Runtime at Four Different Loads
Use the average AC power drawn by everything the battery will supply during the period you are estimating.
Runtime (hours) ≈ available battery energy (kWh DC) × conversion efficiency ÷ average AC load (kW)
| Average AC load | 5 kWh available | 10 kWh available |
|---|---|---|
| 300 W | 15 hours | 30 hours |
| 500 W | 9 hours | 18 hours |
| 1,000 W | 4.5 hours | 9 hours |
| 2,000 W | 2.25 hours | 4.5 hours |
These are generic calculations. The table excludes additional inverter standby consumption and assumes the battery and inverter can sustain each listed load. Use the efficiency and operating limits for the actual system when making a selection.
Use the Energy Available When the Outage Starts
Check whether a capacity figure describes nominal energy, usable battery energy, or energy delivered at the AC output. The table above uses usable energy at the battery’s DC output. If your data sheet already states AC energy delivered, divide that figure by the AC load directly. Our guide to kW, kWh, and usable energy explains how to read those ratings.
Starting charge matters just as much as installed capacity. Suppose your system has only 3 kWh available above its discharge limit when the power fails. At 500 W and the same 90% efficiency assumption, the estimate becomes 3 × 0.90 ÷ 0.50 = 5.4 hours.
Ask your installer how the backup reserve works in your system. Some settings hold energy for an outage and release it when the grid fails. Others define the point at which discharge stops. The available energy depends on both the starting charge and the settings used during backup.
A 500 W Evening Load for Eight Hours
Suppose the circuits you want to keep running average 500 W from 10 p.m. to 6 a.m. They need 0.50 kW × 8 hours = 4 kWh at the AC output.
A fully available 5 kWh battery would deliver an estimated 4.5 kWh AC at 90% conversion efficiency. That leaves 0.5 kWh in the example for load variation, before any extra standby consumption. A 10 kWh battery under the same assumptions would deliver 9 kWh AC.
Use measured consumption from the selected circuits where possible. Refrigerators and air conditioners cycle, and an evening with electric cooking can look very different from one with only refrigeration, lights, and internet equipment. To build a load list from individual appliances, follow How to Size a Home Backup Battery.
Check What Can Run Together
A runtime calculation assumes the system can supply the requested power. Check the inverter’s backup output and the battery’s discharge limit, including the starting demand of compressors and pumps. A motor can require a brief surge even when its energy use over an hour is modest.
Also confirm which circuits receive backup power. The installation may supply selected circuits or a larger part of the home. The Australian Government’s battery guidance describes these differences and the need to manage loads during an outage. Read the battery backup guidance. For the questions to raise with your installer, see Will a Home Battery Work During a Power Outage?.
For longer outages, check how the system will recover its charge between discharge periods. Our home battery charging time guide works through that calculation.
Send MINGWATT your essential-load list, target runtime, and existing inverter model. Include measured overnight consumption if you have it.