1. Understand the Difference Between kW and kWh
A load drawing 1 kW for two hours uses 2 kWh of electricity. A 2 kW load running for one hour also uses 2 kWh, but the inverter must supply twice as much power while it runs.
| Specification | What it measures | What it tells you |
|---|---|---|
| kW | Power | How much power a device draws or a system can supply at a given time |
| kWh | Energy | How much electricity a battery stores or a load uses over time |
| Ah | Electric charge | Battery capacity expressed in amp-hours. Use the nominal voltage to estimate energy in kWh. |
To work from your own appliances and target runtime, see How to Size a Home Backup Battery.
2. Estimate Nominal Energy from Voltage and Amp-Hours
If a data sheet lists nominal battery voltage and capacity in amp-hours, you can estimate nominal energy with this formula.
Nominal energy (kWh) ≈ nominal voltage (V) × capacity (Ah) ÷ 1,000
For example, a battery rated at 51.2 V and 100 Ah has an estimated nominal energy of 5.12 kWh. A 25.6 V, 100 Ah battery has an estimated nominal energy of 2.56 kWh. The two batteries have the same Ah rating, but the higher-voltage battery in this example stores roughly twice as much energy.
For product comparisons, check the manufacturer’s published energy rating and the conditions used to determine it.
3. Compare Nominal Energy, Usable Battery Energy, and AC Energy
Nominal energy is the battery’s rated energy. Usable battery energy is the energy available from the battery over the specified discharge range and under the stated conditions. AC energy delivered is the energy available to household loads at the inverter’s AC output.
Here is a worked example for a hypothetical battery and inverter.
| Energy figure | Example value | Basis |
|---|---|---|
| Nominal battery energy | 5.12 kWh | 51.2 V × 100 Ah ÷ 1,000 |
| Usable battery energy | 4.60 kWh | Assumed DC-side rating over the specified discharge range |
| Estimated AC energy delivered | 4.14 kWh | 4.60 kWh × 90% assumed conversion efficiency |
At a steady 500 W AC load, 4.14 kWh would provide about 8.3 hours in this example. That estimate assumes the full 4.60 kWh is available when the outage starts and excludes any standby consumption beyond the assumed conversion losses. A lower starting state of charge, a higher backup reserve, battery aging, or different operating conditions can reduce runtime.
If a specification already gives energy delivered at the AC output, use that figure directly under its stated conditions. Applying inverter losses again would count them twice.
4. Check Continuous and Peak Power
The continuous discharge rating tells you what the battery can sustain under the stated conditions. The peak discharge rating applies for a limited time. Look for the duration alongside the number. A peak rating that lasts only a few seconds may be relevant for starting a motor, while an appliance that runs for minutes or hours must fit within the system’s continuous limits.
Read battery and inverter ratings at their respective points in the system. A battery’s DC discharge rating and an inverter’s AC backup output rating describe different points in the power path. The achievable backup output depends on both, as well as the battery voltage, conversion losses, and any operating limits.
If you are pairing a battery with an existing inverter, use How to Check Battery–Inverter Compatibility to verify the exact models and operating limits.
What to Compare on Two Battery Data Sheets
- Energy. Compare usable kWh at the same measurement point, either battery DC or inverter AC.
- Test conditions. Check temperature, discharge rate, and the stated state-of-charge range when available.
- Power. Compare continuous discharge ratings and check both the peak rating and its duration.
- System configuration. Confirm whether each rating applies to one module, multiple modules, or a complete system with an inverter.
For help reading a specification, share the data sheets you are comparing, your essential loads, and the backup time you need.