How Long Can a 15kWh Home Battery Power a House?

A battery rated at 15 kWh nominal can supply a steady 500 W AC load for about 24.8 hours, or a 1 kW load for about 12.4 hours, assuming 90% usable DC energy and 92% inverter efficiency. These estimates start with the full usable energy available, without recharging or additional standby losses. They are generic calculations, not performance ratings for a MINGWATT model.

Whether that covers your house depends on which circuits stay on. A refrigerator, lights, and a router create a different energy budget from a home also running air conditioning, electric cooking, and water heating.

How the Runtime Calculation Works

First find the energy available to the appliances. In this example:

15 kWh nominal × 0.90 usable fraction = 13.5 kWh DC
13.5 kWh DC × 0.92 inverter efficiency = 12.42 kWh AC

Then divide by the average AC load in kilowatts:

Backup time in hours = available AC energy in kWh ÷ average AC load in kW

Calculated runtime from 12.42 kWh AC, with no recharge or additional standby consumption
Steady AC loadCalculationApproximate runtime
500 W12.42 ÷ 0.524.8 hours
1,000 W12.42 ÷ 112.4 hours
2,000 W12.42 ÷ 26.2 hours
3,000 W12.42 ÷ 34.1 hours

Each row assumes the battery and inverter can support that load. Efficiency varies with operating conditions; use the supplier's discharge-efficiency data where available. A full charge-and-discharge round-trip efficiency figure describes a different measurement.

Check What “15kWh” Means on the Data Sheet

If the specified 15 kWh is already usable DC energy, skip the 90% reduction. At the same assumed 92% inverter efficiency, it would provide 13.8 kWh AC, or 13.8 hours at 1 kW.

If the supplier states energy delivered on the AC side, check the test conditions before applying any further conversion loss. Deducting the same loss twice understates runtime. Our guide to nominal capacity and usable energy explains these measurement boundaries.

A Sixteen-Hour Outage With Changing Loads

Household demand rarely stays constant. Here is an illustrative schedule for selected backup circuits, with each figure representing average AC demand over the stated period.

Example load schedule from 6 p.m. to 10 a.m.
PeriodAverage loadAC energy used
6 p.m.–10 p.m.: 4 hours0.80 kW3.20 kWh
10 p.m.–6 a.m.: 8 hours0.25 kW2.00 kWh
6 a.m.–10 a.m.: 4 hours0.60 kW2.40 kWh
Total: 16 hoursVaries by period7.60 kWh

The calculated 12.42 kWh AC covers this schedule with 4.82 kWh remaining before extra demand and uncounted losses. Adding a 2 kW heater for three hours consumes another 6 kWh, taking the total beyond the available energy. That single change matters more than small adjustments to the efficiency assumption.

Build the schedule from measured consumption where possible. For cycling appliances, use energy recorded over several hours. The home backup sizing guide shows how to assemble a load list.

What If the Battery Is Only Partly Charged?

Use energy available above the system's discharge limit when the outage begins. If only 6.75 kWh DC remains available, the example inverter would deliver about 6.21 kWh AC: roughly 12.4 hours at 500 W.

That is half the original usable-energy allowance; it is not a universal interpretation of “50%” on a battery app. Displayed state of charge and reserve settings depend on the system. See how backup reserve settings affect available energy.

Additional standby consumption, temperature, and battery aging can reduce the hours available. Include auxiliary consumption separately only if it is absent from the efficiency or delivered-energy figure being used.

Confirm the System Can Run the Loads

A runtime calculation cannot establish backup capability. The Australian Government's battery guide explains that outage supply depends on system configuration and may cover selected circuits rather than the whole property.

Check continuous and startup power, backed-up circuits, and whether solar can operate and recharge the battery during an outage. The estimates above assume no recharge. Use the 15kWh system selection guide to review the complete setup.

For a MINGWATT enquiry, send your backup circuit list, measured consumption, required hours, and inverter model. These details give a useful basis for discussing capacity and available system options.