Start With the Actual AC Load
A 2000W inverter does not draw 2000W continuously just because that number appears on its label. Its input follows the connected load, plus conversion and standby losses. Add the appliances that may run together, including small loads already operating when a larger appliance starts.
Also check whether the inverter rating is expressed in watts or volt-amperes. They are not interchangeable for every load. For example, Victron's Inverter Smart specification lists separate VA, continuous W, temperature-dependent output, and peak ratings. Read the equivalent fields for the exact inverter being proposed.
Calculate the Battery Current
For a steady load, a useful first estimate is:
DC current = AC load watts ÷ inverter efficiency ÷ DC input voltage
| AC load | At 12.8V DC | At 12.0V DC |
|---|---|---|
| 500W | 43.4A | 46.3A |
| 1000W | 86.8A | 92.6A |
| 1500W | 130.2A | 138.9A |
| 2000W | 173.6A | 185.2A |
The second voltage column shows why checking only nominal voltage can miss a constraint: the same AC output takes more current at a lower input voltage. Use the manufacturer's operating range and the voltage expected at the inverter under load. These are calculation points, not recommended discharge cutoffs.
Suppose one candidate battery permits 150A continuous discharge. A 2000W load already exceeds that limit in both columns. A second candidate rated for 200A continuous clears this simplified steady-current calculation, but still needs checks for temperature derating, startup current, other DC loads, and the installation. Neither rating is a MINGWATT product claim.
Check What Happens When a Load Starts
A refrigerator compressor or pump may demand more power at startup than while running. Compare the appliance's startup requirement with both the inverter's surge capability and the battery's permitted peak-current duration. A peak figure without a duration is not enough.
In a hypothetical case, 3000W AC for two seconds would need about 278A at 12.0V and 90% efficiency. That rough estimate does not capture every transient, but it shows why a 200A continuous specification cannot establish startup capability. Ask for the documented peak limit and a representative load test.
The installer must also check DC cable voltage drop, connections, isolation, and protection against the equipment manuals. Repeated BMS trips are a reason to diagnose the load and installation, not to raise protection thresholds.
Then Estimate Runtime
A nominal 12.8V × 300Ah battery stores 3.84kWh. If 90% of that energy is available and discharge conversion is 90% efficient, the simple AC energy estimate is 3.11kWh:
3.84 × 0.90 × 0.90 ÷ 2.00 ≈ 1.56 hours at 2000W
This assumes a full starting charge, steady load, and no additional losses or early protection shutdown. A 150A-limited pack cannot be assigned that runtime at a load it cannot sustain. See the 300Ah runtime guide for mixed AC and DC loads, and the 300Ah charging-time guide to plan the next recharge.
Bring These Details to a Battery Enquiry
Send the inverter model, continuous and startup loads, required runtime, existing battery arrangement, and installation space. Include the battery's continuous and peak discharge limits if you already have a candidate. The HC battery selection page provides a route to review the application; confirm the available model and specification with MINGWATT rather than treating this generic 300Ah example as a catalogue listing.